Electrical Data UCR

Rated

Min.Cir.

MaxFuse

Rec.

Discon.

Rated

Min.Cir.

Locked

MaxFuse

Rec.

Load Amps

Size Fuse

Switch

Load Amps

Rotor

Size

Fuse

4

Amps

1

(MCA)

2

(MOP)

3,8

Size

4,8

Size

9

Amps

1

(MCA)

2

(LRA)

5

(MOP)

3

Size

UCR030

UCR030AHASAC00S

208V-230V/ 3PH/ 60HZ

114

128

175

150

175

57.0

71.2

425

125

90

UCR030

UCR030AFASAC00S

460V/ 3PH/ 60HZ

52

58

80

70

80

25.8

32.2

173

50

40

UCR030

UCR030ANASAC00S

575V/ 3PH/ 60HZ

41

46

60

60

70

20.6

25.8

128

45

35

UCR050

UCR050AHASAC00S

208V-230V/ 3PH/ 60HZ

188

211

300

250

300

94.0

117.5

605

200

150

UCR050

UCR050AFASAC00S

460V/ 3PH/ 60HZ

85

96

125

110

150

42.5

53.1

272

90

70

UCR050

UCR050AFASAC00S

575V/ 3PH/ 60HZ

68

76

110

90

110

34.0

42.5

238

70

60

UCR070

UCR070AFASAC00S

208V-230V/ 3PH/ 60HZ

246

277

400

325

400

123.1

153.9

599

250

200

UCR070

UCR070AFASAC00S

460V/ 3PH/ 60HZ

111

125

175

150

175

55.7

69.6

310

125

90

UCR070

UCR070AFASAC00S

575V/ 3PH/ 60HZ

89

100

125

125

150

44.5

55.7

239

100

70

NOTES:
1. RLA - Rated Load Amps are calculated as per UL1995.
2. MCA - Minimum Circuit Ampacity is: [ 125% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent motors and/or electrical loads].
3. MOP - Maximum Overcurrent Protection or Max.Fuse Size is rounded down from: [ 225% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent electrical loads].
4. Recommended Dual Element Fuse Sizing: Rounded up from 150% of the RLA of the largest compressor motor plus 100% of the RLA of all other concurrent electrical loads.
5. LRA - Locked Rotor Amps are instantaneous starting amperage per compressor.
6. Module internal wiring is per NEC.
7. Voltage Tolerance Range
208-230V / 60 Hz: Min. 187V Max. 253V
460V / 60 Hz: Min. 414V Max. 506V
575V / 60 Hz: Min. 518V Max. 632V
8. MOP Device or Recommended Fusing Device for Module Power Wiring supplied by others. These are recommended values for electrical power protection of Modules selected.
9. Disconnect Switch for Module Power Wiring supplied by others. These are recommended values for electrical power protection of Modules selected.

Power Wiring - per Module