beautypg.com

Water piping confi gurations drawing – ClimaCool UCR Remote Air Cooled User Manual

Page 17

background image

15

www.climacoolcorp.com

Water Piping Confi gurations Drawing

Notes:

1.

Figures 1 and 2 are required piping for proper water regulation and distribution through ClimaCool modular chillers.

2.

Module order and incoming/outgoing water

fl

ow, as shown in both Figure 1 and 2, can be set up as either a left-to-right or right-to-left con

fi gura-

tion.

3.

For chilled water (evaporator) inlet/outlet location dimensions, refer to page 13 - Dimension Data and Drawings.

4.

A pressure di

ff erential

fl

ow switch is a required safety device for ClimaCool modular chillers on the chilled water circuit.

5.

A strainer with a minimum of 60 mesh stainless steel screen is a required safety to protect the brazed plate heat exchanger

on the chilled water

side of the system.

6. Maximum water

fl

ow rates for the evaporator water header system in one bank of modules is 1000 GPM.

Figure 1- Field Piping Direct Return - 1 to 5 Modules

Figure 2 - Field Piping Reverse Return -(Preferred 1 to 5 modules) Required for 6 to 12 Modules