beautypg.com

Schreiber Chillers MICRO MAX CHILLERS User Manual

Page 7

background image

7

Schreiber Engineering – Air Cooled Water Chiller

Model MICRO MAX series


This unit is pre-wired for 230/1.

To test unit as follows. NOTE: Make sure the switch on the panel is at “OFF” position.

Connect the water system loop as follows. The discharge from chiller water pump to heat
exchanger being cooled, then connect the return water to the chiller return as marked.
These discharge and return fittings are 1/2” NPT. The connecting hose can be rubber or
plastic. However, using rubber hose will require make adaptor at the chiller’s discharge
and return for connection. The pump is factory set to discharge water 4.4 gpm (gallon
per minute) at 60psi. Adjusting the relief valve located at pump discharge can modify
this flow condition. Be sure you use a non-contaminate hose.

Fill the reservoir through the fill pipe on top of the unit. Be sure you replace the cap
when the reservoir’s filled. The water sight glass is marked at the reservoir proper fill
level.

The unit is equipped with a 220v female power plug. A male power plug is supplied with
the unit. Proper wire connection is required with a certified electrical technician.

With input power, 220/1 voltages, supplied to the unit, the controller will display the
discharge water temperature. Turning the main panel switch to “ON” position will starts
the system. This switch activates the control to turn on the pump and the refrigeration
system. The unit leaves the factory with discharge temperature setting at 60

0

F. A 10-

second delay is programmed to the controller to start the refrigeration unit. The
minimum temperature is set 40

o

F and the maximum temperature set is 90

0

F. Refer to the

control setting page for changing discharge temperature.

With the controller set at the proper temperature it will control this temperature within
±1° F.

The unit is equipped with a low-pressure switch and high-pressure switch. These
switches are inter-connected to the controller. These switches are there to protect the
refrigeration system from leaking or overload. The low-pressure switch is set at 25 PSI
and the high-pressure switch is set at 425 PSI. If any of the situations is occurring, the
controller will automatically turn off the condensing unit. The controller will display
“L1” or “H1”, which indicate the refrigeration system is being shut off due to pressure.

If the system is off at low pressure, display “L1”, fix the leak and recharging the system
will reset the switch. If the system is off at high pressure, correct the problem and press
the red button to reset the switch.