resulting in a marked decrease in pump performance. This failure is not covered
by warranty. A filter is available as an option to install to the chiller. However
the water initially placed in the reservoir must be clean.

• The reservoir level must be maintained to the level marked on the sight glass.

Damage to the evaporator can result due to low water level.

• Plumbing must be rubber hose, PVC, or copper. Use of any other material will

increase the chance of contamination in the chilled water system.

• The chilled water reservoir is not pressurized. Do not plumb two chillers in series.

• The MICRO MAX chiller is installed with a strainer on the return line to keep

foreign particles out of the system.