beautypg.com

Trouble shooting - part i – Schreiber Chillers 30AC User Manual

Page 14

background image


TROUBLE SHOOTING - PART I

SYMPTOM

DIAGNOSIS

REMEDY






Compressor won't run





Check
Power

supply

Electrical

circuit


Check

Line load voltage

Temperature

control

Compressor

overload

Low pressure switch

High pressure switch

Manual

switch

Compressor
All

control

circuit


Correct circuit breaker
Repair or replace bad circuit


Correct voltage condition
Repair or replace
Replace
Repair or replace
Repair or replace
Replace
Replace
Repair


Compressor runs
No refrigeration


Refrigerant leak
Stuck expansion valve


Repair leak and recharge
Replace expansion valve



High pressure trips


Condenser motor
Air over condenser restricted
Service panel not in place


Repair or replace motor
Clean condenser
Install service panel


Low pressure switch
Cutting out


Defective expansion valve
Refrigerant leak


Replace expansion valve
Repair leak



Temperature too high


Dial thermometer
Temperature controller
Water pump off


Re-adjust or replace
Replace
Check controls circuit



Temperature too cold


Temperature controller
Dial thermometer
Water pump


Repair or replace
Out of adjustment
Not circulating water



15