Condenser is designed to operate in a high ambient condition, 120F. This provides the

flexibility on the installation location without special requirement. However, proper

ventilation is still required. Refrigerant head pressure control is provided by a variable

speed drive. It will vary the speed of both fans based on the highest of the two head

pressure as measured by the controller.

Pumping System

The 15MEDGEN2 will have two identical chilled water pumps. The pumps have stainless

steel housings and impellers. Under normal operating conditions, one of the two pumps

will supply water to the heat exchangers. In the event of a pump failure the controller

will shut down the primary pump and start the backup pump. The reverse is also true.

When fault occurs on the back up pump, the pump will turn off and the primary pump

starts. When both pumps are failed, the controller will go into city water bypass mode,

if the equipment is available. The controller will automatically rotate the pumps

operation to balance operating time. The default change over time is 11PM, and it can

be changed.

The 15MEDGEN2 contains a large chilled water reservoir, 70 gallons. This chilled water

reservoir provides a thermal buffer to help maintain a constant chilled water

temperature to the system. The tank is a non pressurized rectangular tank that is

vented to the atmosphere. To prevent overflowing of the reservoir, a backflow kit it

provided.

The reservoir has 3 layers; a stainless steel inner layer, 1” of foam insulation, and a

powder coated steel outer layer. The top of the tank is made of a stainless steel

insulated and gasket lid.

The reservoir also includes a level sight glass, overflow, fill port for water and glycol,

and drain.

The chiller features two 2-horsepower pump that provide 20GPM @ 50-psi. The

advantage of the system provides a back up fluid supply if the operating pump fails. In

addition, a supply and a return connection provide an easy method to incorporate

emergency back up device such as city water switch over module. An automatic water

pressure valve is equipped to maintain water pressure NOT to exceed 45-psi.

Due to voltage fluctuation at site, a voltage/phase monitor will be installed on the

control system. The tolerance for this device is +10% at the rated condition. There

will be faults indication provided.

Each pump is connected with unions and hose fittings for easy removal if required.

There are discharge pressure gauge, flow switch, 40 mesh wye strainer, and a pressure

relief bypass valve.