At the end of the setpoints screen is the compressor rotation screen. Rotation should be

enabled.

Turn on compressor 1 (pump 1 must still be on) . If the setpoint is below the current

tank temperature the compressor will start. The fan will start after a short delay, and

will slowly ramp up to speed. Scroll through the current status screens to check return

temperature of pump 1., and head pressure of compressor 1. Record pump,

compressor and fan amp draws, and fan operating speed (Hz)

System 2:

At the ON/OFF screen, turn off compressor 1, and then turn on compressor 2. The

rotation will now automatically change from FORWARD to REVERSE. Compressor 2 will

now cycle to maintain the tank temperature.

If required, lower the set-point to force this compressor to cycle

When the compressor cycles, check the head pressure and amp draw. Record these

values.