8. Repeat #5 testing, carefully checking for ground, directly between each

compressor terminal (C, S, & R) and ground.

9. If once again a ground is indicated, proceed to properly replace the compressor,

as it has failed and cannot be repaired.

10. It is important to note that a volt-ohmmeter may be used only to check the

resistance and/or continuity of the motor windings. This may be done as follows:

(a) For internal overload protected motor-compressor, the overload is located

between the common terminal of the compressor and the common motor

lead inside the compressor. If the resistance reading between Common

and Start or Common and Run is open (infinity) and the resistance reading

between Start and Run indicates winding Resistance Values in the

Tecumseh Hermetic Compressor Service Data Book, then the internal

protector is open and time must be allowed for it to reset. Any Common

and Start, Common and Run, and Start and Run resistance reading must

be within the values shown in Tecumseh Hermetic Compressor Service

Data Book.Three phase internal overloads open all three phases.

Therefore, allow time for reset.

(b) For external overload protected motor-compressors, the continuity of the

overload may be checked. The resistance of all winding may also be

checked, i.e., C-S, C-R, and S-R.

(c) Any lack of continuity (other than test indicating an open internal protector)

or improper resistance, indicates a faulty or damaged motor and the

compressor must be properly replaced, as it has failed and cannot be

repaired.

If the above indicates no problem with the compressor, then carefully reconnect the

leads to the proper compressor terminals (C, S, & R); correctly replace the terminal

PROTECTIVE COVER, gasket (if required), and the bale strap.

Then proceed to conduct similar ground and continuity test from the three lead

connection points which you previously disconnected, forward toward the incoming

power connections, to find the electrical problem. DO NOT reset the ground fault

protective device until you have located and corrected the problem. Refer to the Unit

Wiring Diagram and Service Manual for the proper procedure and wiring checkout.

The text of step-by-step procedures uses language and symbols which refer to the

electrical supply as single phase. Three-phase equipment should be given equally

cautious consideration when service is necessary.