2. If you would like to receive email alerts at high and low thresholds, enter values (in

amps) in the “High” and “Low” fields.

These amperage values must correspond to the range you selected with the jumper on
your Current Loop:

If you put the jumper on...

In “High” and “Low,” you may enter...

High (0 – 50 A)

0 to 50

Middle (0 – 20 A)

0 to 20

Low (0 – 10 A)

0 to 10

3. In “Sensor Label,” you may leave the default, “Analog Sensor 1” (or 2) or enter a more

descriptive label of up to 15 characters, such as “AC Power Draw.”

4. Click

Accept Changes

at the bottom of your screen.

5. Click

Save Settings

in the navigation bar to the left of your screen.

Current Loop Features & Specifications

Environment Condition Monitored .................. Electrical current (amps)
Type Of Sensor ................................................... Switch
Power Supply ...................................................... Induced from monitored conductor
Included Sensor Cable Type ............................. Low-voltage 2-wire speaker cable
Included Sensor Cable Length .......................... 25'

Maximum Sensor Cable Length ....................... 100'
Output Voltage ................................................... 0 to 5 VDC
Input Amperage Range ..................................... 0 to 50 A
Accuracy ............................................................. +/- 1.0% (2 to 100% FSO)
Response Time .................................................... < 100 mS
Operating Frequency Range ............................. 50 to 600 Hz
Isolation Voltage ................................................. 2,200 VAC
Maximum Sensing Current Voltage
................. 600 VAC
Aperture (Hole) Size
.......................................... 0.75" (Accepts cables up to 350 MCM)
DIN Rail Size ...................................................... 35 mm
Operating Temperature Range......................... -15 to 40º C (5 to 104º F)
Operating Humidity Range ............................... 0 to 95% RH, non-condensing
Enclosure Rating ................................................ UL94-5VB
Compatible Products ........................................ Room Alert Analog Sensor (built-in or external)