Current Loop (RMA-CL1-SEN)

AVTECH.com

2

3. Wrap the Current Loop around a single

insulated conductor. Examples are
shown here.

4. Before you close the Current Loop,

check the surfaces of the magnetic core
to be sure they’re clear. They need
good contact for the Current Loop to
operate correctly.

5. Lock the Current Loop closed by

pressing the cover down firmly and
listening for the click.

Connect Your Current Loop To Room Alert

Your Current Loop comes with one end of the 25' speaker wire
already attached to its + / - contacts.

Follow these steps to attach the other end of the 25' speaker
wire to the input ports on your built-in or external Room Alert
Analog Sensor:

1. Separate and strip the free ends of the speaker wire. Expose about ¼" of wire.

2. Look at the + / - contacts on the Current Loop and note which

wire is attached to each contact.

3. Insert the unattached end of the “-” speaker wire into the

RIGHT dry contact of the Analog Sensor Input port.

4. Insert the unattached end of the “+” wire into the LEFT dry

contact of the Analog Sensor Input port.

Do not connect Current Loop or Room Alert dry contacts to live circuits.
Use only low-voltage 2-wire cable to connect your Current Loop to Room Alert.

Mount Your Current Loop

Mount the base of the Current Loop on a surface using the included self-drilling mounting
screws or snap it directly on to a 35 mm DIN rail.

Leave a minimum of 1" between the Current Loop and any other magnetic device(s).

Configure Your Current Loop

Navigate to

Settings

Æ

Sensors

in the web interface of the Room Alert, and then scroll down

to “Analog Sensor Settings.”