AVTECH Current Loop 1 (RMA-CL1-SEN) User Manual
Page 2

Current Loop (RMA-CL1-SEN)
AVTECH.com
2
3. Wrap the Current Loop around a single
insulated conductor. Examples are
shown here.
4. Before you close the Current Loop,
check the surfaces of the magnetic core
to be sure they’re clear. They need
good contact for the Current Loop to
operate correctly.
5. Lock the Current Loop closed by
pressing the cover down firmly and
listening for the click.
Connect Your Current Loop To Room Alert
Your Current Loop comes with one end of the 25' speaker wire
already attached to its + / - contacts.
Follow these steps to attach the other end of the 25' speaker
wire to the input ports on your built-in or external Room Alert
Analog Sensor:
1. Separate and strip the free ends of the speaker wire. Expose about ¼" of wire.
2. Look at the + / - contacts on the Current Loop and note which
wire is attached to each contact.
3. Insert the unattached end of the “-” speaker wire into the
RIGHT dry contact of the Analog Sensor Input port.
4. Insert the unattached end of the “+” wire into the LEFT dry
contact of the Analog Sensor Input port.
Do not connect Current Loop or Room Alert dry contacts to live circuits.
Use only low-voltage 2-wire cable to connect your Current Loop to Room Alert.
Mount Your Current Loop
Mount the base of the Current Loop on a surface using the included self-drilling mounting
screws or snap it directly on to a 35 mm DIN rail.
Leave a minimum of 1" between the Current Loop and any other magnetic device(s).
Configure Your Current Loop
Navigate to
Settings
Æ
Sensors
in the web interface of the Room Alert, and then scroll down
to “Analog Sensor Settings.”