Alpha Technologies AlphaCell OPzS User Manual
Page 40

OPzS-BATTERY
40
14.0
Specifi cations, continued
Battery Water Quality Maximum Impurities (Parts per Million (PPM))
Requirements
Maximum Allowable Limits
Total Solids
350.0
Fixed Solids
200.0
Organic and Volatile
150.0
Iron
4.0
Chloride
25.0
Ammonium (NH4)
4.0
Nitrates (NO2)
10.0
Nitrates (NO3)
10.0
Manganese
0.07
Calcium and Magnesium
40.0
Table 14-9, Demineralized Water Impurities
«
List of Reference Standards
Stationary lead-acid batteries. General requirements and methods of test Part 1. Vented types.
EN60896-1, IEC 896-1
Sulphuric acid for use in lead-acid batteries
BS3031
Sulphuric acid and water for use in lead-acid batteries
DIN 43 530-1
Stationary lead-acid batteries accessories
DIN 40 740
Stationary lead-acid batteries - tubular positive plates
DIN 40 736
Safe operation of starter batteries
BS 6604
Safety reqs for secondary batteries and battery installations Part 2: Stationary lead-acid batteries
EN50 272-2 (VDE 0510)
Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid
Batteries for Stationary Applications
IEEE 450
Recommended practice fro installation design and installation of vented lead-acid batteries for
stationary applications (ANSI/BCI)
IEEE 484
Sizing lead-acid batteries for stationary applications (BCI)
IEEE 485
Table 14-10, List of Reference Standards
«