3 factory ranges and defaults – Alpha Technologies Cordex HP CXRF 48-12kW User Manual
Page 32
9400000-J0 Rev C
30
9.3 Factory Ranges and Defaults
Table D shows the rectifier settings/ranges/defaults. Changes are made through the CXC interface.
Table D —
Rectifier factory ranges and defaults
Setting
Range (minimum to maximum)
Default
Float (FL) Voltage
47.5 – 58.2 V
54 V
Equalize (EQ) Voltage
49.8 – 60.2 V
55 V
Battery Test (BT) Voltage
44 – 52 V
46 V
Over Voltage Protection (OVP)*
63 V
57 V
Current Limit (CL)
23 – 100%
100%
Power Limit (PL)
0 – 100%
100%
Module Start Delay
0 – 250 s
1 s
System Start Delay
0 – 600 s
0 s
Low Voltage Alarm (LVA)
42 – 52 V
44 V
High Voltage Alarm (HVA)
52 – 63 V
55.5 V
EQ Timeout
1 – 2399 h
30 h
BT Timeout
1 – 250 h
8 h
Softstart Ramp-rate
Normal/Fast
Normal
CL/PL Alarm
Enable/Disable
Enable
Remote Shutdown
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
*The OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 51.0 V.