7 Maintenance

Although very little maintenance is required with Argus systems, routine checks and adjustments are
recommended to ensure optimum system performance. Qualified service personnel should do repairs.

The following table lists a few maintenance procedures for this system. These procedures should be performed at
least once a year.

WARNING: HIGH VOLTAGE AND SHOCK HAZARD.

Use extreme care when working inside the shelf while the system is energized.
Do not make contact with live components or parts.

Circuit cards, including RAM chips, can be damaged by static electricity. Always wear a grounded
wrist strap when handling or installing circuit cards.

Procedure

Date Completed

Clean ventilation openings

Inspect all system connections (re-torque as necessary)

Verify alarm/control settings

Verify alarm relay operation

Table C–Sample maintenance log

Refer to the specification section at the front of this manual for replacement parts.

7.1

Lithium Battery Replacement

A removable lithium battery is located near the back and to the right of the motherboard. The battery life is rated
up to three years, but should be replaced if the panel does not maintain date and time during power interruption. It
is also recommended to replace when the lithium battery voltage is less than 2.6Vdc.

WARNING
Exercise extreme caution and do not touch any connected equipment.

To replace the lithium battery, shut down the CXC, remove the rear cover, and pull battery out carefully. Ensure
that the new battery is the same as the one being replaced.

NOTE: Replace the battery within 30 seconds to prevent loss of date and time.