beautypg.com

Specifications – Alpha Technologies Continuity: 6K_10K User Manual

Page 34

background image

0170012-J0 Rev A

32

Model

6000 VA

10000 VA

Input

Voltage range

160 to 280 VAC (1Φ)

Frequency

45 to 65 Hz

Phase/wire

Single, Line + Neutral + Ground

Power factor

Up to 0.99 at 100% linear load

Current THD (100% linear load)

< 6%

Output

Voltage window

208/220/230/240 VAC Selectable

Voltage adjustment

±0%; ±1%; ±2%; ±3%

Voltage regulation

±2%

Capacity

6000 VA**

10000 VA**

Rated power factor

0.9 lagging

Wave form

Sine Wave, THD <3% (no load to full load)

Frequency stability

±0.2% (free running)

Frequency regulation

±1Hz; ±3Hz

Transfer time

0 ms

Crest factor

3:1 acceptable

Efficiency (AC to AC, normal)

Up to 91%

Efficiency (AC to AC, ECO)

Up to 97%

Up to 93%

Autonomy

≥ 6 min.

≥ 4 min.

DC start

Yes

Battery

Type

Sealed lead acid

maintenance free

12V / 7Ah

Sealed lead acid

maintenance free

12V / 9Ah

Quantity

20 pcs

Voltage

240 VDC

Recharge Time

4 hours to 90%

Display

Status on LED + LCD

Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low, Battery Bad/

Disconnect, Overload, Transferring with interruption, and UPS Fault

Readings on LCD

Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,

Battery Voltage, and Inner Temperature.

Self-diagnostics

Upon power-up, front panel setting and software control, 24-hour routine checking

Alarms

Audible and visual

Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions

7.  Specifications