Specifications – Alpha Technologies Continuity: 6K_10K User Manual
Page 34
0170012-J0 Rev A
32
Model
6000 VA
10000 VA
Input
Voltage range
160 to 280 VAC (1Φ)
Frequency
45 to 65 Hz
Phase/wire
Single, Line + Neutral + Ground
Power factor
Up to 0.99 at 100% linear load
Current THD (100% linear load)
< 6%
Output
Voltage window
208/220/230/240 VAC Selectable
Voltage adjustment
±0%; ±1%; ±2%; ±3%
Voltage regulation
±2%
Capacity
6000 VA**
10000 VA**
Rated power factor
0.9 lagging
Wave form
Sine Wave, THD <3% (no load to full load)
Frequency stability
±0.2% (free running)
Frequency regulation
±1Hz; ±3Hz
Transfer time
0 ms
Crest factor
3:1 acceptable
Efficiency (AC to AC, normal)
Up to 91%
Efficiency (AC to AC, ECO)
Up to 97%
Up to 93%
Autonomy
≥ 6 min.
≥ 4 min.
DC start
Yes
Battery
Type
Sealed lead acid
maintenance free
12V / 7Ah
Sealed lead acid
maintenance free
12V / 9Ah
Quantity
20 pcs
Voltage
240 VDC
Recharge Time
4 hours to 90%
Display
Status on LED + LCD
Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low, Battery Bad/
Disconnect, Overload, Transferring with interruption, and UPS Fault
Readings on LCD
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,
Battery Voltage, and Inner Temperature.
Self-diagnostics
Upon power-up, front panel setting and software control, 24-hour routine checking
Alarms
Audible and visual
Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
7. Specifications