2.4 Bypass Switch Selection Guide)
Table 1 – Bypass Model Selection Guide
Configuration
CFR 3000 or Smaller
CFR 4000 or CFR 5000
1600 EP
18 KVA
Input
Output
MBB
BBM
MBB
BBM
MBB
120V
120V
BPS 2M3P
Figure 6.1
BPS 2B3P
Figure 6.1
BPS 2M3P
Figure 6.1
BPS 2B3P
Figure 6.1
Not
Applicable
120V
120V
208V
BPS 2M3P
Figure 6.2
BPS 2B3P
Figure 6.2
BPS 2M3P
Figure 6.2
BPS 2B3P
Figure 6.2
120V
120V
240V
BPS 2M3P
Figure 6.3
BPS 2B3P
Figure 6.3
BPS 2M3P
Figure 6.3
BPS 2B3P
Figure 6.3
208V
120V
BPS 2M3P BPT
3000-S or BPT
3000
Figure 6.5
BPS 2B3P
Figure 6.4
BPS 2M3P BPT
5000-S or BPT
5000
Figure 6.5
BPS 2B3P
Figure 6.4
208V
120V
208V
BPS 2M3P BPT
3000
Figure 6.7
BPS 2B3P
Figure 6.6
BPS 2M3P BPT
5000
Figure 6.7
BPS 2B3P
Figure 6.6
208V
120V
240V
BPS 2M3P BPT
3000-S or BPT
3000
Figure 6.8
BPS 2B3P BPT
3000-S or BPT
3000
Figure 6.8
BPS 2M3P BPT
5000-S or BPT
5000
Figure 6.8
BPS 2B3P BPT
5000-S or BPT
5000
Figure 6.8
BPS 3M3P
SC25BK
Figure 6.8
240V
120V
BPS 2M3P
Figure 6.9
BPS 2B3P
Figure 6.9
BPS 2M3P
Figure 6.9
BPS 2B3P
Figure 6.9
Not
Applicable
240V
120V
208V
BPS 2M3P BPT
3000
Figure 6.7
BPS 2B3P BPT
3000
Figure 6.7
BPS 2M3P BPT
5000
Figure 6.7
BPS 2B3P BPT
5000
Figure 6.7
240V
120V
240V
BPS 2M3P
Figure 6.11
BPS 2B3P
Figure 6.11
BPS 2M3P
Figure 6.11
BPS 2B3P
Figure 6.11
BPS 3M3P
Figure 6.11
230V
230V
50Hz
BPS 2M3P
Figure 6.12
BPS 2B3P
Figure 6.12
BPS 1M3P
Figure 6.12
BPS 2B3P
Figure 6.12
Not
Applicable
Notes:
The bypass system consists of the bypass switch (BPS) and bypass transformer if required (BPT).
References to Figures indicate applicable connection diagram.
N/A indicates the configuration is not available for this model of UPS.
MBB = Make Before Break Switch (Provides uninterrupted transfer).
BBM = Break Before Make Switch (Output will be interrupted for at least 30 milliseconds).
Explanation of Bypass Switch ordering code:
BPS xyzz
x = 1 :
40 Amp contact rating
x = 2 :
80 Amp contact rating
x = 3 :
125 Amps contact rating
y = M :
Make-Before-Break contacts
y = B :
Break-Before-Make contacts
zz = 3P : 3 pole switch
•
•
•
•
•
The Alpha BPS Series