0200018-J0 Rev C

6

The Alpha MBS is a manually operated mechanical switch for use with the Alpha series of Uninterruptible

Power Supplies (UPS). It provides a simple and effective means for bypassing uninterruptible power sup-

plies (UPS) while maintaining continuity of power to critical loads. (A schematic at the end of the manual

shows the MBS with the Alpha AMPS80 HP power system.)
Normally the output to the critical load is powered by the UPS with the bypass switch in the NORMAL

(UPS) position. Before the UPS is taken off-line for service or maintenance, the bypass switch can be

switched to the BYPASS position and the critical loads then receive power directly from the utility supply.
The Alpha MBS includes the following safety features:
• Phase detector with lock out
• Safe-to-switch (IN PHASE) lamp
• Electromechanical manual override
• Auxiliary contacts for remote monitoring
• Padlock bar for lockout

3.  Features

3.1  Phase Detector with Lock-out

Bypass mode is enabled when UTILITY IN is within plus or minus 15 degrees of UPS OUT. The phase

difference is displayed in the phase meter at the bottom of the front panel in the range 0-360°.

15°

345°

In Phase Bypass Enabled

Manual switch

Bar for lockout

with a padlock

Phase meter

IN PHASE lamp

Electro-mechanical

key-operated switch