IntegRated ContRols / A+CLASS

APCS DS TID

A+CLASS

DAyLight SenSor

Technical Installation Data

© 2013 alera lighting, a division of Hubbell lighting, Inc. Because of continuing product improvement programs, alera lighting reserves the right to change specifications
without notice. 701 Millennium Blvd. greenville, sC 29607 / tel 864.678.1000 / Website www.aleralighting.com

US Patent #8,436,542

cHAnGinG DAYLiGHt sensor settinGs

Perform these changes only if necessary to ensure proper daylight sensor interaction with the CCM (Classroom Control Module). IN MOsT CAsEs
THE sTANDARD FACTORY sETTING OF 3-300 FC WIll BE OPTIMAl. It is not recommended changes to the setting be made unless footcandle
readings shown in the DAYlIGHT menu of the CCM dictate that this change is necessary. see CCM Operating Manual for further details.

1. Gently remove cover from back of daylight sensor, taking care not to lose it (see Figures 9a and 9b).

Fig. 9b

Fig. 9a

Fig. 10

2. Change sensor setting, first remove the black pin cap. Take care not to lose the black pin cap (see Figure 10).

3. To change setting re-insert black pin cap as shown below (see Figures 11a, 11b and 11c).

a. To set at 30-300 FC insert black pin cap above top two pins, placed horizontally as shown (see Figure 11a).

b. To set at 30-3000 FC, place black pin cap over center two pins, placed horizontally as shown (see Figure 11b).

c. To set at 60-6000 FC insert black pin cap over bottom two pins, placed horizontally as shown (see Figure 11c)

Fig. 11a

Fig. 11c

Fig. 11b