OM--01216

0 SERIES

OPERATION

PAGE C -- 4

Before checking for the source of the leak, check
the point of installation of the vacuum gauge.

STOPPING

Manual Stopping

In the manual mode, reduce the throttle speed
slowly, and allow the engine to idle briefly before
switching the HAND-OFF-AUTO switch to ‘OFF’.

If the application involves a high discharge

head, gradually close the discharge

throttling valve before stopping the pump.

After stopping the pump, switch off the engine igni-
tion and disconnect the positive battery cable to
ensure that the pump will remain inoperative.

Automatic Stopping

In the automatic mode, the pump will stop when
the liquid in the wet well or sump lowers and acti-
vates the “Off” float switch(s). The pump will restart
automatically when the liquid rises and activates
the “On” float switch(s).

Safety Shutdown System

The unit is equipped with a safety system to auto-
matically shut down the engine under certain con-
ditions. The engine will automatically shut down:

1. If the engine exceeds its safe operating tem-

perature.

2. If the engine oil pressure drops below design

limits.

3. If the engine fails to start within a pre-set peri-

od of time.

4. If the engine speed exceeds the safe operat-

ing range.

5. If the engine fan belt breaks.

Lights on the control panel will indicate which of the
safety features has caused the engine to shut
down.

Should any of the safety features cause the engine
to shut down,

the cause must be determined and

corrected before putting the unit back into service.
The engine

will not restart until the HAND-OFF-

AUTO switch has been returned to the ‘OFF’ posi-
tion for at least 10 seconds.

All safety shutdown features are pre-set at the fac-
tory for optimum performance and safety;

do not

attempt to adjust these settings.

Never disconnect any of the safety shut-

down features; this will void the warran-

ty and could result in serious damage to

the unit and/or injury to personnel. Safe-

ty shutdown features are pre-set at the

factory; do not attempt to adjust any of

the settings. Determine the cause of

shutdown before putting the unit back

into service. Consult the factory for ad-

ditional information.

OPERATION IN EXTREME HEAT

The safety shutdown system will automatically
stop the unit if engine operating temperature ex-
ceeds design limits. If engine over-temperature
shutdown occurs, allow the unit to cool before re-
starting.

If engine overheating continues, check the engine
lubricant level and viscosity. Consult the engine
operation manual for the recommended lubricant
for operation in extreme heat.

If the unit is equipped with the optional auto-start
control, the float(s) may need to be adjusted to al-
low shorter run and longer cooling periods, if pos-
sible.

If the pump is equipped with the option-

al automatic starting system, it is sub-

ject to automatic restart. Keep hands

and clothing away from the unit to pre-

vent injury during automatic operation.

Disconnect the battery before perform-