beautypg.com

John Wood Takagi - 240H-340H-540H User Manual

Page 43

background image

43

Page

PROBLEM

SOLUTIONS

W

ATER HE

ATER

Unit does not ignite

when water goes

through the unit.

• Is the flow rate over 1.9 L/min (0.5 GPM)? (p. 36)

• Check for the filter on cold water inlet. (p. 41)

• Check for reverse connection and cross connection.

• If you use the remote controller and/or temperature controller, is

the power button turned on?

• Check if the inlet temperature is too high.

The fan motor is

still spinning after

operation has stopped.

• This is normal. After operation has stopped, the fan motor keeps

running from 15 to 70 seconds in order to re-ignite quickly, as well

as purge all the exhaust gas out of the flue.

Temper

atur

e c

on

tr

olle

r and

Remot

e c

on

tr

oller

Controller does not

display anything when

the power button is

turned on.

• Make sure the unit is supplied with power.

NOTICE:

When the unit has not operated for five minutes or more, the display

of the controllers turns off to conserve energy.

Although the controller of the parent unit will be displayed the set

temperature at the Easy-Link system, the controller of the child unit

will not display the set temperature.

An ERROR code is

displayed.

• Please see p. 44-46.

EAS

Y-LINK

SY

STEM

T-H3-D

V /

540H

only

How are the unit

numbers assigned?

• For an Easy-Link system, the Parent unit is always labeled #1 and all

other subsequent Child units are numbered randomly.

• To check which numbers are assigned to which Child units, push the

button on the computer board of any Child unit as shown below.

The unit number will be displayed on the remote controller. (Refer

to p. 26-29)

Butt on to check unit numbers

When the remote

controller turned

ON, STAND BY LED

is lit.

Temperature controller

Troubleshooti ng

Owner's Guide