TECHNICAL SPECIFICATIONS

Threaded Connections:

1", 1-1/4", 1-1/2" FNPT with Unions

Flanged Connections:

2", 2-1/2", 3" & 4" ANSI150 CLASS

Materials: Body:

Steel

Air Vent:

Brass

Drain Valve:

Brass

Insulation – Threaded:

PEX

Insulation – Flanged:

Polyurethane Foam

Medium:

water, glycol solution non-hazardous, therefore

excluded from the guidelines of 67/548/EC Directive

Maximum Percentage of Glycol:

30% Threaded

50% Flanged

INSTALLATION INSTRUCTIONS

The hydraulic separator is installed between the primary and

secondary circuits, always in a vertical position.
Make sure that all connections are water-tight.
When making the water connections, take care not to over-

tighten the connections to the reducer. Failure to follow these

instructions could result in property damage and/or personal

injury.
During the installation, commissioning and maintenance of

hydraulic separators, all necessary steps should be taken to en-

sure that system water temperature does not cause danger to

people.

DESCRIPTION

The Bell & Gossett’s PSH is a device which makes the primary

and secondary circuits connected to it independent and can

be used on hot or chilled water systems.
The PSH is supplied with an air-vent and check valve assem-

bly to permit automatic discharge of the air in the circuits. The

PSH is also equipped with a drain valve for removing any

impurities deposited in the bottom of the unit.

The PSH should be sized according to the maximum flow rate

at the inlet. The selected value must be either that of the pri-

mary circuit or of the secondary, whichever is the greatest.

Connection Size

1" 1-1/4" 1-1/2" 2" 2-1/2" 3"

4"

Flow Rate (gpm) 11

18

26

40

80

124 247

OPERATING DATA

With Insulation

Working Pressure: 150 psi

Operating Temperature – Threaded: 32°-210°F

Operating Temperature – Flanged: 32°-220°F

Without Insulation

Working Pressure: 150 psi

Operating Temperature – Threaded and Flanged: 32°-230°F

PSH

Primary-Secondary Header

Flanged & Threaded Connections

SAFETY

INSTRUCTION

This safety alert symbol will be used in this manual to draw

attention to safety related instructions. When used, the safety

alert symbol means

ATTENTION! BECOME ALERT! YOUR

SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE IN-

STRUCTIONS MAY RESULT IN A SAFETY HAZARD.

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

CAUTION: All work must be performed by qualified

personnel trained in the proper application, installa-

tion, and maintenance of systems in accordance with all

applicable codes and ordinances.

WARNING: State of California Residents

This product contains a chemical known by the State

of California to cause cancer. This product contains a

chemical known by the State of California to cause birth

defects or other reproductive harm.

WARNING: System fluids are under pressure or temp-

erature can be hazardous. Be sure the pressure has

been reduced to zero and the system temperature is below

100°F (38°C). Failure to follow these instructions could

result in property damage and/or personal injury.

INSTRUCTION MANUAL

V58912B