4.4 Shuttle Register List

SHUTTLE

“Offset Read

Default”

Type

Register

name

Explanations

LowB

HighB

#

Status Com.
Module

#

Shuttle

226

227

B16

Status Error
bit 1-16

0 = OFF, 1 = ON
Bit 1: Measurement OK (No delay)
Bit 2: Measurement Error (Inversed Measurement OK 1
min ON Delay)
Bit 3: Sensor Error (Inversed Measurement OK 10min
ON Delay)
Bit 4:Temperature Error (if not between -50° and 80° and
has 1min ON delay)

228

229

S16

Signal quality

Signal Quality [%] 0(Error) - 100%(Highest / best)

230

231

S32

{Low}

Level

Level -2E9 - 2E9 [mm]

232

233

S32

{High}

-

234

235

S32

{Low}

Distance to

surface

Distance to surface -2E9 - 2E9 [mm]

236

237

S32

{High}

-

238

239

S16

Temperature

Teperature (Error if not between -50° and 80°C)