iLink - Configuration and Support Utility
iQuest (NZ) Ltd - PO Box 15169 HAMILTON Tel: +64 7 957 8160 - Fax: +64 7 957 8162 - Email: [email protected]
6.3.3.3 Callback Cfg
These settings, with the exception of ‘Enable daily callback’ and ‘Time for daily callback’, are also used by
the logger for a callback following a triggered alarm (if set).
Callback via
{Internal Modem, RS232 Port}
Specify here whether the logger will use its internal modem to callback (via radio or PSTN/cellphone
mode) or its RS232 port (via external modem or cellular device). This setting is also used for alarm-
generated callbacks.
Enable daily callback
If enabled, the logger will automatically callback once per day at the time specified.
Time for daily callback
If ‘Enable daily callback’ is enabled, this setting tells the logger at what time to callback.
Base
Specify the base address here. Under normal circumstances this would be left at the HydroTel 2000
default of zero. This setting is also used for alarm-generated callbacks.
Base phone number
If callbacks are to be performed via a PSTN/cellphone link, the number to dial is specified here. This
setting is also used for alarm-generated callbacks.
6.3.3.4 Lookup Table
The DS-4483 logger is able to store a single lookup table for performing derived sensor calculations. For
example, it may be necessary or useful to have the flow rate derived from a stage level sensor within the
logger and utilized as a separate value. The lookup must be in the correct format.
File Name
Enter the file name of the lookup table here.