13.10.2 Sequence for automatic test run
Time Test Run
100 h
Adjustable between 1...100 hours.
The test run starts the pump at the set time after
the last stop for 20 seconds with the in parameter 13.10.3 set speed.
Deactivating test run: Set 0 hours, by using Ï
and Ð.
Repeating the test run: Select test run and set the desired hours using the key
Ï
.
Press
Î
on the controller to change to
13.10.3 Test Run: Frequency
Test Frequency
30.0 Hz
Frequency for manual and automatic test run.
Can be set from 0 Hz up to 70 Hz.
Press
Î
on the controller to change to
13.10.4 Test Run: Boost
BOOST Test Run
10.0 %.
Start voltage in % of rated voltage in order to ensure
that the motor starts safely. Adjustable between 0%
and 25%
To leave the submenu press the Î key longer than 3 sec.!
13.11 Submenu Error
Submenu
Error
To enter this menu you have to press the Ð
key, to
leave the menu, press the Î key longer than 3 sec.
13.11.1 Conveyor Limit
Conveyor Limit
0.0 bar
Disabled or adjustable between 0 and 10 bar of the
analogue input signal range.
“0.0 bar” means disabled conveyor limit.
An adjusted value >0 has to be reached till the programmed “ERROR DELAY”-time.
Doesn’t this value be reached the failure “ERROR WATER” will be indicated and the
pump stops.
Press
Î
on the controller to change to
13.11.2 Error Delay