Xylem HV 1.1 - 1.2 User Manual
Page 11

11
5
Technical Data - Frequency Inverter And General Data
HYDROVAR
Hydrovar output to
the Motor
Supply Voltage (Uin)
Prefuse
min.
Type Rated
output
Voltage Max.
current
Mains frequency
48-62 Hz
HV 1.1
1,1 kW
3x 230 V
4,8 A
1x 220-240 V±15%
10 Ampere
HV 1.15
1,5 kW
3x 230V
7,0 A
1x 220-240 V ±15%
10 Ampere
HV 1.2
2,2 kW
3x 230V
10,0 A
1x 220-240 V ±15%
16 Ampere
Output voltage:
3x 0...Uin VAC / 0-70 Hz
(depends on the input voltage)
Min. frequency:
0 – max. frequency
Electrical efficiency:
> 95%
Protection
against: Short circuit, over- and undervoltage, overheating of the
electronics (overload) and additional external protective functions
via PTC (motor temperature) and low water switch.
A mains filter is fitted to ensure interference immunity.
The HV Series frequency converter complies with the general EMC provisions and has
been tested according to the following standards:
• Disturbance voltage:
EN 55011
• EMC – Immunity:
EN 61000-4-3 and ENV 50204
• Electrostatic discharge:
EN 61000-4-2
Ambient temperature:
5° C ... + 40°C
Storage temperature:
-25° C ... + 55° C
(+70°C during max. 24 hours.)
Humidity:
rH max. 50% at 40°C, unlimited
rH max. 90% at 20°C, max. 30 days per year
Condensation not permitted !
Air pollution:
The air may contain dry dust as found in workshops where
there is no excessive quantity of dust due to machines.
Excessive amounts of dust, acids, corrosive gases, salts etc.
are not permitted
Altitude::
max. 1000m above sea level
At higher altitudes the max. available power has to be
reduced. Please ask the manufacturer for further details.
Class of protection :
IP55