Caution – Xylem IM205 Vortex Series User Manual
Page 17

Vortex Installation, Operation and Maintenance Manual
15
Oil Level
Put the pump in a horizontal position so that the 2 hexagonal socket screws 
are on top and one at the bottom (see Figure 11). Unscrew the level plug 
(1) and the vent plug (2).
The oil level should be at the lower side of the openings (see drawing). By 
turning the pump a bit this should be visible. If not, fill up to the correct 
level.
Always use the right kind of oil.
Oil Change
Collection, storage and removal of the oil should be done according to the 
regulations of the local authorities.
Figure 10
When necessary replace the sealing rings.
Always use the right kind of oil. (See Figure 10).
Put the pump in a horizontal position so that one of the oil plugs is at the 
bottom. Remove the vent plug (2). Put a receiving bin underneath the drain 
plug (1). Remove the plug and drain the oil.
Rotate the pump so that the 2 openings are on top.
Refill the oil housing. The oil level should be at the lower side of the 
openings. Replace the plugs.
Motor Housing
Unscrew the inspection plug of the motor 
housing. Put the pump in horizontal 
position with the inspection opening 
downwards. If water is present it will run 
out this way. A small amount of water, 
due to condensation is permissible. More 
water is an indication of leakage of the 
seal or housing. Oil is an indication of 
seal failure between motorhousing and oil 
chamber. Motor chamber is air filled only.
Figure 11
Hazardous pressure can
cause personal injury or
property damage.
CAUTION
Hazardous pressure can
cause personal injury or
property damage.
CAUTION
2
1
2
A
1
B
2
1
C
1
2
Hazardous pressure can
cause personal injury or
property damage.
CAUTION
Routine Maintenance (continued)
1
Hazardous pressure can
cause personal injury or
property damage.
CAUTION
