TABLE 8 — 12" Three Phase Motors, 380 and 460 volt
Motor Type Rated Rated Line-Line Maximum Motor Lead Size
Power Voltage KVA
Resistance
Water Temp.
Three Phase HP kW V Code
Ω
ºF (ºC)
Sec. AWG
L
DOL
Y/D Ft. (m)
P12..250T386A
250 185
380
H
–
86
2x3/0 4/0 16.4
P12..250T466A
460
0.044
(30)
2x2/0 2/0 (5)
P12..300T386A
300 220
380
H
0.059
86
2x4/0 – 16.4
P12..300T466A
460
0.034
(30)
2x3/0 4/0 (5)
P12..350T386A
350 260
380
G
0.041
86
– – 16.4
P12..350T466A
460
0.027
(30) 2x4/0 – (5)
P12..400T386A
400 300
380
H
0.036
86
– – 16.4
P12..400T466A
460
0.021
(30) – – (5)
Operation (continued)
Motor Rating
75º C Insulation - AWG Copper Wire Size
Volts HP 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500
5.5 147 234 371 555 939 1494 2376 2997 3781 4765 6006 7574 8950 12530
230V 7.5
106 166 264 395 669 1064 1691 2133 2691 3392 4277 5394 6371 8920 12744
60 Hz.
10
0
133
210 314 531 845 1342 1694 2138 2694 3397 4283 5059 7083 10120
Three 15
0
0
147
221 374 594 946 1192 1504 1894 2389 3013 3560 4982 7118
Phase 20
0
0
0
170
288 458 728 918 1160 1462 1843 2323 2746 3843 5491
3 Lead
25
0
0
0
0
229
363 578 730 920 1160 1461 1843 2178 3048 4355
30 0 0 0 0
197
264 498 629 794 1000 1259 1589 1877 2627 3754
5.5
629
1000
1589
2374
4016
6349
7.5 467 742 1179 1762 2982 4744 7541 9509
10 362 574 912 1363 2304 3667 5830 7352 9277
12.5
294 467 744 1110 1878 2970 4752 5992 7560 9530
15
253 400 637 950 1610 2560 4069 5131 6475 8162 10290
20
187 298 472 706 1195 1901 3022 3811 4810 6061 7642
460V 25 0
248 395 589 997 1576 2522 3179 4013 5058 6376 8040
60 Hz. 30 0 0
322 480 813 1285 2054 2592 3270 4122 5197 6552 7741
Three 40 0 0 0
357 603 960 1525 1923 2427 3059 3856 4862 5746
Phase 50 0 0 0
278 472 749 1192 1502 1896 2389 3013 3798 4488 6283 8976
3 Lead 60 0 0 0 0
397 627 1003 1264 1595 2011 2534 3197 3776 5286 7552
75 0 0 0 0 0
517 822 1037 1309 1648 2078 2621 3096 4336 6194
100 0 0 0 0 0 0
613 773 976 1230 1550 1957 2310 3235 4622
125 0 0 0 0 0 0
496 624 789 994 1253 1579 1866 2611 3731
150 0 0 0 0 0 0 0 0
576 726 915 1155 1365 1910 2728
200 0 0 0 0 0 0 0 0 0 0
765 963 1139 1594 2277
Lengths NOT SHADED meet the U.S. National Electrical Code ampacity for either individual conductors or jacketed 75º C cable.
Lengths
SHADED meet the National Electric Code ampacity only for individual conductor 75º C cable, in free air or water. If other cable is used, the
National Electric Code as well as the local codes should be observed.
IX. Three Phase 75º C Cable, 60 HZ
TABLE 9 — Three Phase 75º C Cable, 60 Hz (Service Entrance to Motor) Maximum Length in Feet