1.0 GENERAL DESCRIPTION

1.1 The MiniBooster pumping packages will increase the

domestic water pressure at the fixtures from 20 to 55
PSI above that of the city water pressure.

1.2 Depending upon the pumping capacity required, a

Simplex (one pump) type or a Duplex (two pump)
type is used. In both types, a pressure switch starts
and stops the pump(s).

1.3 PURPOSE OF MANUAL

1.4 This manual is furnished to acquaint you with some

of the practical ways to install, operate, and maintain
this unit. Read it completely before doing any work
on your unit and keep it handy for future reference.

1.5 Equipment cannot operate well without proper care.

To keep this unit at top efficiency, follow the recom-
mended installation and servicing procedure outlined
in this manual.

1.6

SAFETY INSTRUCTION

1.7 This safety alert symbol will be used in this manual to

draw attention to safety related instructions. When
used the safety alert symbol means ATTENTION
BECOME ALERT! YOUR SAFETY IS INVOLVED!
FAILURE TO FOLLOW THIS INSTRUCTION MAY
RESULT IN A SAFETY HAZARD.

1.8 ADDITIONAL SAFETY REQUIREMENTS

1.9 Always use accurate test meters when checking elec-

trical components. Always work with another person
in case of emergency.

1.10 STORAGE

1.11 For long periods of storage, the unit should be cov-

ered to prevent corrosion and contamination from
dirt. It should be STORED in a clean, dry location
between 0 and 170°F. The relative humidity should
not exceed 85%. The unit should be checked period-
ically to ensure that no condensation has formed.
After storage, again check that it is dry before apply-
ing power.

1.12 HANDLING

1.13 Care should be taken to prevent damage due to

dropping or jolting when moving the MiniBooster.
Transportation damage should be brought to the
carrier's attention immediately upon receipt.

1.14 TEMPERATURE AND VENTILATION

1.15 All electrical equipment is susceptible to failure if

operated in ambient temperatures outside of its rat-
ing. The OPERATING temperature range for this unit
is 32 to 105°F. The relative humidity should not
exceed 95% non-condensing. The unit should not be
operated outside these extremes.

1.16 ELECTRICAL CONNECTIONS - A.C. POWER &

SIGNALS INPUT VOLTAGE

1.17 The input voltage tolerance is +10/-10% of name-

plate voltage.

1.18 GROUND CONNECTIONS

1.19 A grounding terminal is provided for a dedicated

ground wire connection. All provisions of the National
Electrical Code and local codes must be followed.

1.20 POWER WIRING

1.21 Power wire types and sizes must be selected based

upon conformance with the National Electrical Code
and all local codes and restrictions. In addition, only
copper (Cu) wire rated for at least 75°C may be used
for the power connections. Refer to the input current
as listed on the motor nameplate when sizing wire.

1.22 FIELD CONNECTION DIAGRAMS

1.23 Refer to the 3530 pump Installation, Operation, and

Maintenance manual for specific details unique to the
pump.

1.24 The following field connection diagrams should be

reviewed prior to unit installation and operation.

Drawing #

Description

Page

1MBD02

Piping: Simplex

8

1MBD03

Piping: Duplex

9

1SWD01 or
1SWD02

Wiring, Simplex (shipped w/ unit)

1SWD03

Wiring, Duplex (shipped w/ unit)

1380 _ _

Unit specific Drawing (shipped w/ unit)

WARNING: ELECTRICAL SHOCK HAZARD. IN-
SPECT ALL ELECTRICAL CONNECTIONS PRIOR TO

POWERING THE UNIT. WIRING CONNECTIONS MUST
BE MADE BY A QUALIFIED ELECTRICIAN IN ACCOR-
DANCE WITH ALL APPLICABLE CODES, ORDINANCES,
AND GOOD PRACTICES.

FAILURE TO FOLLOW THESE INSTRUCTIONS COULD
RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.

WARNING: CONDUIT GROUNDS ARE NOT ADE-
QUATE. A SEPARATE GROUND WIRE MUST BE

ATTACHED TO THE GROUND LUG PROVIDED IN THE
ENCLOSURE TO AVOID POTENTIAL SAFETY HAZARDS.

FAILURE TO FOLLOW THESE INSTRUCTIONS COULD
RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.

WARNING: PREVENT ELECTRICAL SHOCKS. DIS-
CONNECT THE POWER SUPPLY BEFORE BEGIN-

NING INSTALLATION.

FAILURE TO FOLLOW THESE INSTRUCTIONS COULD
RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.