beautypg.com

3 installation, 1 mounting, 2 cooling – Crown Audio Macro-Tech Series (600, 1200 & 2400) User Manual

Page 10

background image

Macro-Tech 600/1200/2400 Power Amplifiers

Page 10

Reference Manual

If the air supply is unusually dusty, you might want to
pre-filter it using commercial furnace filters to prevent
rapid loading of the unit’s own air filter. When needed,
the unit’s filter can be cleaned with mild dish detergent
and water (see Section 4.5).

BLOWER

(OPTION 2)

BLOWER

(OPTION 1)

AIR

FLOW

FRONT

OF

RACK

DOOR

AIR

FLOW

EQUIPMENT

RACK

(SIDE VIEW)

Fig. 3.3 Proper Air Flow in a Rack Cabinet

3 Installation

3.1 Mounting

Macro-Tech amplifiers are designed for standard
19-inch (48.3-cm) rack mounting and “stack” mounting
without a cabinet. For more efficient cooling and extra
support in a rack, it is recommended that units be
stacked directly on top of each other.

Important: If the unit will be transported, it should also
be securely supported at the back of the rack.

Fig. 3.2 Top View of a Rack-Mounted Unit

AIR

FLOW

AIR FLOW

AMPLIFIER

(TOP VIEW)

RACK

CABINET

16 in

40.6 cm

2 in

(5 cm)

MIN.

IMPORTANT: Be sure rear of amplifier

is securely mounted to rack.

17 in

43.2 cm

AIR

FLOW

3.2 Cooling

NEVER block the side or front air vents. Macro-Tech
amplifiers do not need to be mounted with space be-
tween them. If you must leave open spaces in a rack
for any reason, close them with blank panels to prevent
air from recycling into the front of other amplifiers. Allow
at least 35 cubic feet (1 cubic meter) per minute per
unit for the Macro-Tech

600 and 1200, and at least 45

cubic feet (1.3 cubic meters) per minute per unit for the
Macro-Tech 2400. Additional air flow may be required
when driving low impedance loads at consistently high
output levels. Refer to Section 7 for detailed information
on thermal dissipation.

Fig. 3.1 Mounting Dimensions

19 in

48.3 cm

16 in

40.6 cm

3.5 in
8.9 cm

2.5 in

6.35 cm

SIDE VIEW

LEVEL

LEVEL

ON

OFF

30

27

24

21

18

15

12

9

6

3

0

ENABLE

CH1

CH2

ODEP

30

27

24

21

9

6

3

0

SIGNAL / IOC

18

15

12

When mounting the amplifier in a rack, the side walls of
the rack should be at least 2 inches (5 cm) away from
the chassis as shown in Figure 3.2.

Tip:

An easy way to verify adequate cooling is to ob-

serve the ODEP indicators while the amplifier is operat-
ing under worst-case conditions. If the indicators dim,
additional cooling is recommended.

If your rack has a front door that could block air flow to
the amplifier’s air intakes, you must provide adequate
air flow by installing a grille in the door or by pressuriz-
ing the air behind the door. Wire grilles are recom-
mended over perforated panels because they tend to
cause less air restriction. A good choice for pressuriz-
ing the air behind a rack cabinet door is to mount a
“squirrel cage” blower inside the rack (Option 1 below).
At the bottom of the rack, mount the blower so it blows
outside air into the space between the door and in front
of the amplifiers, pressurizing the “chimney” behind the
door. This blower should not blow air into or take air out
of the space behind the amplifiers. For racks without a
door, you can evacuate the rack by mounting the
blower at the top of the rack so that air inside the cabi-
net is drawn out the back (Option 2 below).