beautypg.com

12 c, Ac b, Installation to solid concrete or cinder block – Peerless-AV ESHV20 - Installation User Manual

Page 5: Warning, Fi g. 1.1 fi g. 1.2

background image

5 of 27

ISSUED: 01-17-11 SHEET #: 083-9013-1

Remove end cap with bubble level from
column (A) as shown in fi gure 1.1. Make sure
that column (A) is level, use it as a template
to mark two mounting holes. Drill two 5/16" (8
mm) dia. holes to a minimum depth of 2"
(51 mm). Insert anchors (C) in holes fl ush with
wall as shown. Place column (A) over anchors
and secure with two M5 X 44mm wood screws
(B).

Tighten fasteners then cover M5 X 44mm
wood screws (B) with screw covers (H) as
shown in fi gure 1.2.

1

Installation To Solid Concrete or Cinder Block

When installing Peerless wall mounts on cinder block, verify that you have a minimum of 1-3/8"
(35 mm) of actual concrete thickness in the hole to be used for the concrete anchors. Do not drill
into mortar joints! Be sure to mount in a solid part of the block, generally 1" (25 mm) minimum
from the side of the block. Cinder block must meet ASTM C-90 specifi cations. It is suggested
that a standard electric drill on slow setting is used to drill the hole instead of a hammer drill to
avoid breaking out the back of the hole when entering a void or cavity.

• Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete

anchor.

• Installer must verify that the supporting surface will safely support the combined load of the

equipment and all attached hardware and components.

WARNING

WARNING

C

A

CINDER BLOCK

H

B

CONCRETE

A

fi g. 1.1

fi g. 1.2

concrete
surface

1

2

C

Drill holes and insert anchors (C).

Place column (A) over anchors (C) and secure
with screws (B). Tighten all fasteners.

A

C

B

CUT

A

W

A

Y

VIEW

INCORRECT

CORRECT

column

column

plaster/

dry wall

plaster/

dry wall

concrete

concrete

• Tighten screws so that column is

fi rmly attached, but do not overtighten.
Overtightening can damage screws, greatly
reducing their holding power.

• Never tighten in excess of 80 in. • lb (9

N.M.).

• Always attach concrete expansion anchors

directly to load-bearing concrete.

• Never attach concrete expansion anchors

to concrete covered with plaster, drywall,
or other fi nishing material. If mounting to
concrete surfaces covered with a fi nishing
surface is unavoidable, the fi nishing
surface must be counter bored as shown
below. Be sure concrete anchors do not
pull away from concrete when tightening
screws. If plaster/drywall is thicker than
5/8" (16 mm), custom fasteners must be
supplied by installer.

END CAP