No.

UPS STATUS

ACTION

6

AC utility power fails .The load is

supplied by battery power. Buzzer alarm

sounds every 4 seconds.

If AC utility power fails,

reduce the less critical

load in order to extend

backup time. If it is not

abnormal power failure,

please check the rated

input or connected line.

7

AC utility fails. UPS is in battery backup

mode and battery power is approaching

low level. Buzzer alarm beeps every

second.

UPS will shut down

automatically. Please

save data soon.

8

AC utility power fails and battery runs

out. UPS has shut down automatically.

UPS will restart up when

AC utility power is

restored. If AC utility

power failure is more

than 6 hours, please

follow storage

instruction.

17

7. OPERATION MODES OF THE UPS

7.1 UPS System Block Diagram

7.2 Normal Operation

There are two main loops when AC utility is normal: the AC loop and the

battery charging loop. The AC output power comes from AC utility input and

passes through AC/DC rectifier, DC/AC inverter and static switch to support

power to load. The battery charging voltage comes from AC utility input and

converted by AC/DC charger to support battery-charging power.