5~9. Load & Battery Capacity LEDs:

(a) No. 5 to 8 LED is green color and No. 9 (used as warning LED for

overload or battery low) is yellow.

(b) These LEDs show the load % of the UPS if the mains power is

available (in normal operation). LEDs light up to indicate the following

information.

No. 5 LED: 0-35 %

No. 5&6&7&8 LEDs: 76-95 %

No. 5&6 LEDs: 36-55 %

No. 5&6&7&8&9 LEDs: 96-105%

No. 5&6&7 LEDs: 56-75 %

(c) In the battery operation, the LEDs indicate the capacity (%) of the

batteries. LEDs light up to indicate the following information.

No. 9 LED: 0%-25 % (battery low level)

No. 8&9LEDs: 26%-50 %

No. 6&7&8&9 LEDs: 76%-95 %

No. 7&8&9 LEDs: 51%-75 % No. 5&6&7&8&9 LEDs: 96-100 %

10. Fault LED (red): To indicate the UPS is in fault condition because of

inverter shutdown or over-temperature

11. On/Test/Mute key: It should be pressed with the control key (see the

following item 12) simultaneously to do UPS auto test and turn off the

buzzer when in battery operation.

12. Control Key:

(a) When this key is pressed with the On/Test/Mute key simultaneously

for 3 seconds, the UPS will be switched on after two beeps.

(b) When UPS is in operation, press this key and On/Test/Mute/ key

simultaneously, the UPS will do auto battery test. And the Battery LED

will blink if the battery may have problem. Besides, in battery operation

(buzzer beeps), press this key and the On/Test/Mute key at the same

7

time to disable the buzzer.

(c) When UPS is in operation this key is pressed with the Off key

simultaneously for 3 seconds, the UPS will be switched off after two

beeps

13. Off key: It should be pressed with the control key (see the above item 12)

simultaneously to switch off the UPS.

LCD Version

1. LCD Display: This indicates the UPS operation information, including UPS

status, input/output voltage, input/output frequency, battery voltage, battery

capacity left, output load, inside temperature, and the times of history

events.

2. LCD Select Up-key: It is pressed to select upward the UPS status on LCD

Display.

3. LCD Select Down-key: It is pressed to select downward the UPS status on

LCD Display. Beside, press it simultaneously with the Up-key to switch off

the UPS.