6 Set up with the indicating and adjustment module

VEGAPULS 66 • HART and accumulator pack

40933-EN-121011

The menu item "Extend" is used to extend an already created false

signal suppression. This is useful if a false signal suppression was

carried out with a too high level and not all false signals could be de-

tected. When selecting "Extend", the distance to the product surface

of the created false signal suppression is displayed. This value can

now be changed and the false signal suppression can be extended to

this range.

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. in a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the

vessel is displayed correctly. If the volume should not be displayed in

percent but e.g. in l or kg, a scaling can be also set in the menu item

"Display".

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [ESC] and [->] key.
Caution:

Note the following if the instrument with corresponding approval is

used as part of an overfill protection system according to WHG:
If a linearisation curve is selected, the measuring signal is no longer

linearly proportional to the level. This must be taken into consideration

by the user, particularly when setting the switching point on the level

switch.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.

Additional adjustments/

Linearization curve

Additional adjustments

- Reset