6 Set up with the display and adjustment module
VEGAFLEX 83 • Foundation Fieldbus
44227-EN-130910
The instrument carries out an automatic false signal suppression
as soon as the probe is uncovered. The false signal suppression is
always updated.
The menu item "Delete" is used to completely delete an already cre-
ated false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
To damp process-dependent measured value fluctuations, set an
integration time of 0 … 999 s in this menu item.
If you have selected interface measurement under the menu item
"Application", you can adjust the damping for the level and the inter-
face separately.
The default setting is a damping of 0 s.
A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. a horizontal cylindri-
cal or spherical tank, when the indication or output of the volume is
required. Corresponding linearization curves are preprogrammed
for these vessels. They represent the correlation between the level
percentage and vessel volume.
The linearization applies to the measured value indication and the
current output. By activating the appropriate curve, the volume per-
centage of the vessel is displayed correctly. If the volume should not
be displayed in percent but e.g. in l or kg, a scaling can be also set in
the menu item "Display".
Warning:
If a linearization curve is selected, the measuring signal is no longer
necessarily linear to the filling height. This must be considered by the
user especially when adjusting the switching point on the limit signal
transmitter.
In the following, you have to enter the values for your vessel, for
example the vessel height and the socket correction.
For non-linear vessel forms, enter the vessel height und the socket
correction.
For the vessel height, you have to enter the total height of the vessel.
Setup - Damping
Setup - Linearization