Quick start
VEGAFLEX 83 • Foundation Fieldbus
44227-EN-130910
1. In this menu item you can select the application. You can choose
between level and interface measurement.
2. In the menu item "Medium - Dielectric constant" you can define
the type of medium (medium).
3. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
4. A "Linearization" is recommended for all vessels in which the
vessel volume does not increase linearly with the level - e.g. in a
horizontal cylindrical or spherical tank. Activate the appropriate
curve.
5. A "False signal suppression" detects, marks and saves the false
signals so that they are no longer taken into account for level
measurement. We generally recommend a false signal suppres-
sion.
The sensor measures the distance from the sensor (reference plane)
to the product surface.
2
4
5
3
1
2
4
5
3
1
Fig. 3: Measuring ranges - VEGAFLEX 83
1 Reference plane
2 Probe length L
3 Measuring range (default setting refers to the measuring range in water)
4 Upper dead band (in this area no measurement is possible)
5 Lower dead band (in this area no measurement is possible)
Parameterization example