beautypg.com

VEGA VEGAFLEX 83 Foundation Fieldbus PFA insulated User Manual

Page 31

background image

31

6 Set up with the display and adjustment module

VEGAFLEX 83 • Foundation Fieldbus

44227-EN-130910

You can find "Extended adjustment" in the next sub-chapter.
Application

In this menu item, you can select the application. You can choose

between level measurement and interface measurement. You can

also choose between measurement in a vessel or in a bypass or

standpipe.

Medium - dielectric constant

In this menu item, you can define the type of medium (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Dielectric constant - upper medium

In this menu item, you can define the type of medium (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

General information

Level measurement

Interface measurement