5 levelmaster commands – VEGA VEGABAR 86 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 69
69
10 Supplement
VEGABAR 86 • Modbus and Levelmaster protocol
46296-EN-131107
10.5 Levelmaster commands
The VEGABAR 86 is also suitable for connection to the following RTUs with Levelmaster protocol.
The Levelmaster protocol is often called "Siemens" "Tank protocol".
RTU
Protocol
ABB Totalflow
Levelmaster
Kimray DACC 2000/3000
Levelmaster
Thermo Electron Autopilot
Levelmaster
Parameters for the bus communication
The VEGABAR 86 is preset with the default values:
Parameter
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8
Parity
None, Odd, Even
None
Stop Bits
1, 2
1
Address range Levelmaster
32
32
The Levelmaster commands are based on the following syntax:
•
Capital letters are at the beginning of certain data fields
•
Small letters stand for data fields
•
All commands are terminated with "
•
All commands start with "Uuu", whereby "uu" stands for the address (00-31)
•
"*" can be used as a joker for any position in the address. The sensor always converts this in
its address. In case of more than one sensor, the joker must not be used, because otherwise
several slaves will answer
•
Commands that modify the instrument return the command with "OK“. "EE-ERROR" replaces
"OK" if there was a problem changing the configuration
Report Level (and Temperature)
Request:
Parameter
Length
Code/Data
Report Level (and Temperature)
4 characters ASCII
Uuu?