6 Set up with the display and adjustment module
VEGABAR 86 • Modbus and Levelmaster protocol
46296-EN-131107
6 Set up with the display and adjustment
module
6.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
and removed any time. Four positions displaced by 90° can be se-
lected. It is not necessary to interrupt the power supply.
Proceed as follows:
1. Unscrew the housing cover
2. Place the display and adjustment module in the requested posi-
tion onto the electronics and turn to the right until it snaps in
3. Screw housing cover with inspection window tightly back on
Removal is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-
ditional connection is not necessary.
Fig. 18: Insertion of the display and adjustment module with single chamber
housing
Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.