VEGA VEGABAR 86 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 55
55
10 Supplement
VEGABAR 86 • Modbus and Levelmaster protocol
46296-EN-131107
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 25 bar/0 … 2500 kPa
130 bar/13000 kPa
0 bar abs.
Nominal measuring ranges and overload capacity in psi
The specifications are only an overview and refer to the measuring cell. Limitations due to the
material and version of the process fitting as well as the selected pressure type are possible. The
specifications on the nameplate apply.
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +0.4 psig
+75 psig
-0.725 psig
0 … +1.5 psig
+225 psig
-2.901 psig
0 … +5 psig
+435 psig
-11.60 psig
0 … +15 psig
+510 psig
-14.51 psig
0 … +30 psig
+725 psig
-14.51 psig
0 … +150 psig
+1300 psig
-14.51 psig
0 … +300 psig
+1900 psig
-14.51 psig
Absolute pressure
0 … 1.5 psi
225 psig
0 psi
0 … 5 psi
435 psi
0 psi
0 … 15 psi
510 psi
0 psi
0 … 30 psi
725 psi
0 psi
0 … 150 psi
1300 psi
0 psi
0 … 300 psi
1900 psi
0 psi
Output variable
Output
Ʋ Physical layer
Digital output signal according to standard EIA-485
Ʋ Bus specifications
Modbus Application Protocol V1.1b, Modbus over serial
line V1.02
Ʋ Data protocols
Modbus RTU, Modbus ASCII, Levelmaster
Max. transmission rate
19.2 Kbit/s
Dynamic behaviour output
Run-up time approx.
10 s
Dynamic characteristics, depending on medium, temperature and, if applicable, chemical seal