beautypg.com

5 connecting to power supply, 1 preparing the connection, 2 connection procedure – VEGA VEGATOR 112 User Manual

Page 10

background image

10

5 Connecting to power supply

VEGATOR 112 •

46106-EN-131217

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

In hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power

supply units.

The voltage supply can be 20 … 253 V AC/DC, 50/60 Hz. You can find

details on the voltage supply in the technical data.

The operating voltage of VEGATOR 112 is connected with standard

cable according to the national installation standards.
The sensors are connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326 for industrial areas, screened cable should

be used.

Connect the cable screen on both ends to ground potential. In the

sensor, the screen must be connected directly to the internal ground

terminal. The ground terminal on the outside of the sensor housing

must be connected to the potential equalisation (low impedance).
If potential equalisation currents are expected, the connection on the

processing side must be made via a ceramic capacitor (e. g. 1 nF,

1500 V). The low-frequency potential equalisation currents are thus

suppressed, but the protective effect against high frequency interfer-

ence signals remains.

Take note of the corresponding installation regulations for Ex applica-

tions. In particular, make sure that no potential equalisation currents

flow over the cable screen. In case of grounding on both sides this

can be achieved by the use of a capacitor or a separate potential

equalisation.

5.2 Connection procedure

For comfortable connection, the pluggable terminals can be removed,

if necessary. For electrical connection, proceed as follows:
1. Mount the instrument as described in the previous chapter
2. Connect sensor cable 1 to terminal 1/2, and where applicable,

connect the screen

3. Connect sensor cable 2 to terminal 4/5, and where applicable,

connect the screen

4. Connect power supply (switched off) to terminal 16/17
5. Connect relay 1 to terminal 10/11/12
6. Connect relay 2 to terminal 13/14/15

Note safety instructions

Take note of safety

instructions for Ex

applications

Select power supply

Select connection cable

Cable screening and

grounding

Select connection

cable for Ex applica-

tions