beautypg.com

VEGA VEGABAR 83 HART and accumulator pack - Operating Instructions User Manual

Page 16

background image

16

4 Mounting

VEGABAR 83 • HART and accumulator pack

45035-EN-131107

1

4

3

2

1

2

3

4

Fig. 8: Measurement setup with process pressure measurement of gases in

pipelines
1 VEGABAR 83

2 Blocking valve

3 Siphon

4 Pipeline

A protective accumulation of water is formed through condensation

in the pipe bends. Even in applications with hot steam, a medium

temperature < 100 °C on the transmitter is ensured.

Keep the following in mind when setting up the measuring system:

Mount the instrument below the measuring point

The effective pressure line is always filled with liquid and gas bubbles

can bubble up to the process line.

Measurement setup in

liquids