beautypg.com

VEGA VEGABAR 81 4 … 20 mA - Operating Instructions User Manual

Page 57

background image

57

11 Supplement

VEGABAR 81 • 4 … 20 mA

45025-EN-131010

Damping (63 % of the input variable),

adjustable

0 … 999 s

Indication value - DIsplay and adjustment module

2)

Ʋ Displayed value 1

Pressure in bar/mbar

Ʋ Displayed value 2

Pressure in bar/mbar

Output variable - Second current output
For details on the operating voltage see chapter "Voltage supply"
Output signal

4 … 20 mA (passive)

Range of the output signal

3.8 … 20.5 mA (default setting)

Signal resolution

0.3 µA

Failure signal current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
Max. output current

21.5 mA

Starting current

≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA

Load

Load resistor, see chapter "Voltage supply"

Damping (63 % of the input variable),

adjustable

0 … 999 s

Dynamic behaviour output
Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 29: Sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response time

1 Process variable

2 Output signal

Dead time

≤ 45 ms

Rise time

≤ 35 ms (10 … 90 %)

Step response time

≤ 80 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

2)

The indication values can be assigned individually