9 Diagnosis, asset management and service
VEGABAR 81 • 4 … 20 mA
45025-EN-131010
Required tools:
•
Hexagon socket wrench, size 2
Caution:
The exchange may only be carried out in the complete absence of
line voltage.
In Ex applications, only a replacement part with appropriate Ex ap-
proval may be used.
Proceed as follows when carrying out the exchange:
1.	 Losen	the	fixing	screw	with	the	hexagon	socket	wrench
2. Carefully detach the cable assembly from the process assembly
1
2
5
3
4
Fig. 28: VEGABAR 81 in IP 68 version, 25 bar and lateral cable outlet, external
housing
1 Process assembly
2 Plug connector
3 Cable assembly
4 Connection cable
5 External housing
3. Loosen the plug connector
4. Mount the new process assembly on the measuring point
5. Plug the connector back in
6. Mount the cable assembly on the process assembly and turn it to 
the desired position
7.	 Tighten	the	fixing	screw	with	the	hexagon	socket	wrench
The	exchange	is	finished.
If there is no replacement part available on site, one can be ordered 
from the agency serving you.
The necessary serial number can be found on the type label of the 
instrument or on the delivery note.