9 Diagnosis, asset management and service

VEGABAR 81 • 4 … 20 mA

45025-EN-131010

Code
Text mes-

sage

Cause

Rectification

M501
Error in the

non-active

linearization

table

– Index markers are not con-

tinuously rising, for examle

unlogical value pairs

– Check linearization table

– Delete table/Create new

M502
Error in the

event memory

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

M504
Error on an

device inter-

face

– Hardware defect

– Check connections

– Exchanging the electronics

– Send instrument for repair

M507
Error in the

instrument

settings

– Error during setup

– Error when carrying out a

reset

– Carry out reset and repeat

setup

9.4 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The first measures are:

Evaluation of fault messages, for example via the display and

adjustment module

Checking the output signal

Treatment of measurement errors

Further comprehensive diagnostics options offer a PC with the soft-

ware PACTware and the suitable DTM. In many cases, the reasons

can be determined in this way and faults can be rectified.

Connect a multimeter in the suitable measuring range according to

the wiring plan. The following table describes possible errors in the

current signal and helps to remove them:

Error

Cause

Rectification

4 … 20 mA signal

not stable

– Fluctuations of

the measured

variable

– Set damping according to the

instrument via the display and

adjustment module or PACTware/

DTM

Reaction when malfunc-

tions occur

Procedure for fault recti-

fication

Check the 4 … 20 mA

signal