4 saving the parameter adjustment data – VEGA VEGAPULS SR 68 HART and accumulator pack User Manual
Page 47
47
6 Set up with the display and adjustment module
VEGAPULS SR 68 • HART and accumulator pack
40934-EN-130624
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Dependent on the sensor:
Liquid/Water
Bulk solids/Crushed stones, gravel
Application
Demonstration
Vessel form
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"Technical data" in the supplement
Min. adjustment
Recommended measuring range, see
"Technical data" in the supplement
Max. adjustment
0,000 m(d)
Damping
0.0 s
Current output
mode
4 … 20 mA, < 3.6 mA
Current output
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Block adjustment Released
Display
Language
Like order
Displayed value
Distance
Display unit
m
Scaling size
Volume
l
Scaling
0.00 lin %, 0 l
100.00 lin %, 100 l
Backlight
Switched off
Additional adjust-
ments
Distance unit
m
Temperature unit °C
Probe length
Length of the standpipe Ex factory
Linearization
curve
Linear
HART mode
Multidrop
Address 1
6.4 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in the operating instructions