beautypg.com

VEGA VEGAPULS SR 68 HART and accumulator pack User Manual

Page 42

background image

42

6 Set up with the display and adjustment module

VEGAPULS SR 68 • HART and accumulator pack

40934-EN-130624

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4. Enter the suitable distance value in m for the empty vessel (e.g.

distance from the sensor to the vessel bottom) corresponding to

the percentage value.

5. Save settings with [OK] and move with [ESC] and [->] to the max.

adjustment.

Proceed as follows:
1. Select with [->] the menu item max. adjustment and confirm with

[OK].

2. Prepare the percentage value for editing with [OK] and set the

cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4. Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. Keep in mind that the max.

level must lie below the min. distance to the antenna edge.

5. Save settings with [OK]

The respective min. and max. measured value is saved in the sensor.

The values are displayed in the menu item "Peak values".

Setup - Max. adjustment

Diagnosis/Peak value