36

6 Adjustment with the display and adjustment module

WEIGHTRAC 31 • Foundation Fieldbus

42375-EN-131120

To increase the Delta I value, you have to increase the distance of the

min. and max. adjustment points in the linearization.

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. through down-

stream indicating instruments or the input card of the control system.
Note:

To carry out a simulation with the display and adjustment module,

you have to switch on the simulation switch on the electronics module

(switch position 1).
You can find the rotary switch on the electronics module in the elec-

tronics and connection department (large cover).
You can simulate different values:

Pulse rate of the sensor

Process value

Switching function of the relay

Information:

10 minutes after the key was pressed for the last time, the simulation

is interrupted automatically. You can also interrupt the simulation with

the switch on the electronics module.
Info
In this menu you will find the following menu items:

Instrument name - shows instrument name and serial number

Instrument version - shows hardware and software version of the

instrument

Diagnosis - Simulation

Info