30

5 Connecting to power supply

WEIGHTRAC 31 • Foundation Fieldbus

42375-EN-131120

5.4 Connection - Tachometer

The speed of the conveyor belt, the chain conveyor or the feed screw

are absolutely necessary for mass flow determination.
There are three different possibilities:

Entering a constant speed

Accepting a speed value from the plant control system (e.g. PLC)

Connecting a tachometer (analogue or digital)

If a constant speed is entered, fluctuations in the speed are not taken

into account. This can cause measurement errors. We recommend

using a real value from the plant control system or the optional

tachometer.
See "Parameter adjustment - Mass flow detection".
If you have entered a constant belt speed, we recommend using a

belt stop signal.
If the belt stops, measurement is also halted for this period. Without

a belt stop signal, WEIGHTRAC 31 would continue summing the

delivery rate.
You can implement the belt stop signal with a switching relay or a

signal from the plant control system (PLC).
Connect a switching relay to terminals 14 and 16.
Connect the digital output signal (open collector) from the plant con-

trol system (PLC) to terminals 14 and 15.
Belt speed - PLC

The shown diode should have a blocking voltage of > 50 V, any type

of diode can be used.
If the output of the PLC is an "open collector", then the diode is not

required.
Tachometer - analogue

Connect the analogue tachometer according to the following illustra-

tion.

Constant belt speed

Belt speed (PLC), ta-

chometer (analogue)