6 Set up with the display and adjustment module
VEGABAR 81 • HART and accumulator pack
45026-EN-131107
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
In the menu item "Lock/unlock adjustment", you can protect the
sensor parameters against unauthorized modification. The PIN is
activated/deactivated permanently.
The following adjustment functions are possible without entering the
PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment mod-
ule.
Caution:
With active PIN, adjustment via PACTware/DTM as well as other
systems is also blocked.
You can change the PIN number under "Additional adjustments -
PIN".
This menu item enables the setting of the requested national lan-
guage.
The following languages are available:
•
German
•
English
•
French
•
Spanish
•
Russian
•
Italian
•
Dutch
•
Portuguese
•
Polish
•
Czech
•
Turkish
Setup - Current output 1
and 2 (min./max.)
Lock/release setup - Ad-
justment
Display - Language