6 Set up with the display and adjustment module
VEGABAR 86 • Profibus PA
45042-EN-131107
– Confirm selected menu
– Edit parameter
– Save value
•
[-] key:
– Presentation, change measured value
– Select list entry
– Select editing position
•
[+] key:
– Change value of the parameter
•
[ESC] key:
– Interrupt input
– Jump to next higher menu
The device is adjusted via the four keys of the display and adjustment
module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration. Ap-
prox. 60 minutes after the last pressing of a key, an automatic reset to
measured value indication is triggered. Any values not confirmed with
[OK] will not be saved.
6.3 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.
Carry out the following steps in the below sequence.
You can find "Extended adjustment" in the next sub-chapter.
1. Sensor address
In the first menu item you have to enter a sensor address. The selec-
tion switches on the electronics module are preset to sensor address
126. This means that the sensor address can be changed via the
display and adjustment module.
2. Measurement loop name
In this menu item you assign a suitable measurement loop name.
Permitted are names with max. 19 characters.
3. Application
In this menu item, you activate/deactivate the slave for the electronic
differential pressure and select the application. The application com-
prises process pressure and level measurement.
Adjustment system
Quick setup - Presettings