VEGAPULS 63 • Modbus and Levelmaster protocol
41364-EN-130228
Input register
The input registers consist of 16 bits. They can only be read out. Before each command, the ad-
dress (1 byte) is sent, after each command a CRC (2 bytes) is sent.
PV, SV, TV and QV can be adjusted via the sensor DTM.
Register Name
Register Number
Type
Note
Status
100
DWord
Bit 0: Invalid Measurement Value PV
Bit 1: Invalid Measurement Value SV
Bit 2: Invalid Measurement Value TV
Bit 3: Invalid Measurement Value QV
PV Unit
104
DWord
Unit Code
PV
106
Primary Variable in Byte Order CDAB
SV Unit
108
DWord
Unit Code
SV
110
Secondary Variable in Byte Order CDAB
TV Unit
112
DWord
Unit Code
TV
114
Third Variable in Byte Order CDAB
QV Unit
116
DWord
Unit Code
QV
118
Quarternary Variable in Byte Order CDAB
Status
1300
DWord
See Register 100
PV
1302
Primary Variable in Byte Order of Register 3000
SV
1304
Secondary Variable in Byte Order of Register 3000
TV
1306
Third Variable in Byte Order of Register 3000
QV
1308
Quarternary Variable in Byte Order of Register 3000
Status
1400
DWord
See Register 100
PV
1402
Primary Variable in Byte Order CDAB
Status
1412
DWord
See Register 100
SV
1414
Secondary Variable in Byte Order CDAB
Status
1424
DWord
See Register 100
TV
1426
Third Variable in Byte Order CDAB
Status
1436
DWord
See Register 100
QV
1438
Quarternary Variable in Byte Order CDAB
Status
2000
DWord
See Register 100
PV
2002
DWord
Primary Variable in Byte Order ABCD (Big Endian)
SV
2004
DWord
Secondary Variable in Byte Order ABCD (Big Endian)
TV
2006
DWord
Third Variable in Byte Order ABCD (Big Endian)
QV
2008
DWord
Quarternary Variable in Byte Order ABCD (Big En-
dian)